On line UPS EA900RT series 1KVA-3KVA
Applications: Rack mounted server and other networking equipment
Features & Benefits:
Rack and tower convertible
High Frequency and double conversion online technology
Fully digitized microprocessor control
Wide input voltage range
Advanced PFC technology
Self-testing when UPS startup
ABM &automatic battery charging in UPS off mode
Lighting and surge protection
Short circuit and overload protection
Network/fax/modem surge protection
Extension battery pack (optional)
LCD display
Smart RS232 communication with monitoring software
SNMP card slot (optional)
Technical Specifications
Model |
EA901RT |
EA902RT |
EA903RT |
Capacity(Linear Load) |
1KVA/700W |
2KVA/1400W |
3KVA/2100W |
Input |
Voltage Range |
Half-Load 120-300VAC, Full-Load 165V-276VAC |
Frequency Range |
50/60Hz¡À10% |
Power Factor |
>0.95 |
Output |
Voltage |
220/230/240V¡À3% |
Frequency |
50/60Hz¡À0.5Hz |
Distortion |
£¼ 3%(Linear Load); £¼ 5%(Non-linear Load) |
Waveform |
True Sine Wave |
Efficiency |
>85% |
Ouerload Capability |
110%~130%: Switch to Bypass after 1Min;130%: Shut down after 1s. |
Crest Factor |
3:1 |
Short Circuit |
UPS turn off output and alarm |
Battery |
Type |
12V7Ah |
Voltage |
35Vdc |
96Vdc |
Confirguration |
3*7Ah Batter |
8*7Ah battery |
Charge Time |
Charging Up to 90% £¬ ¡Ü8 Hours |
Low voltage |
31¡À2V |
81¡À2V |
Others |
Communication Interface |
RS232 (standard) ,SNMP (optional) |
LCD and LED |
Utility, Inverter, Bypass, Battery, Load, Battery Mode, Frequency, UPS Fault Indicator |
Audible Alarm-Battery Discharge |
Utility Failure, Beep/4s; Battery Low, Beep/1s |
EMC |
50091, 9254 |
UPS Abnormal |
Continuous Beep and Red LED on |
Noise Level |
<55dB |
Ambient Temperature |
0 ¡æ ~ 40 ¡æ |
Humidity |
10%~90% |
Weight(Kg) |
9.2/ 13.5KG |
12.5/26Kgs |
Dimension(mm) |
440W¡Á85H¡Á485D |
Packing Measure(mm) |
520W¡Á170H¡Á565D |
|